Aquablend® eSQX™ Touch Free Point of Use Thermostatic Wall Mixer In-Wall Component – Mains

Product Information

Aquablend® eSQX™ is Australia’s first and most technically advanced touch-free thermostatic mixer solution. Designed to deliver touch-free pre-mixed warm water for enhanced infection control and crosscontamination prevention.

  • Integral TMV adjustable temperature ensures ultimate user comfort
  • Low voltage 12V mains power supply
  • Effective reduction of Legionella risk
  • Compatible with Smartflow Monitoring System for TMV monitoring and reporting
  • Back and front of wall components offered may be ordered and supplied separately to meet construction needs
  • Requires eSQX front of wall component
  • Watermark: AS 4032.4 WMKA25301
  • NSW Health Approved
  • Smart Flow Enabled

Pressure

Dynamic Inlet Pressures Min 20kPa Max 500kPa (10% maximum dynamic pressure differential between hot and cold supplies)
Static Inlet Pressure 1000kPa Max (For testing purposes/ system commissioning)

Temperature

Thermostatic Temperature Range 35 to 46 °C (+/- 2 ˚C) (Set during installation/ commissioning)
Minimum Temperature Differential 10˚C (Between hot or cold supply and outlet mix temperature)C

Inlet & Outlet

Inlet Temperatures Cold Supply: Min 5°C Max 25°C Hot Supply: Min 55°C Max 85°C
Inlet Connection 15mm (1/2” BSP)

Flow Rate

Minimum Flow Rate 2 L/minL/min
Product Code Description FINISH
ATM621 Aquablend® eSQX™ Touch Free – On Demand Sensor Point of Use Thermostatic Wall Mixer – Back of Wall Component for Mains Powered Models – ATAM and ATWM Chrome Plating Add to spec